Friday, April 29, 2011

USE-2 CABLE

FOLLOWRAY USE-2 CABLE meeting UL 854 requirements.
1.Cable design
1.1 Conductor: fine wire strands of tinned copper wires,according IEC 60228,Class 5
1.2 Insulation:Flame retardant PE,electron beam cross-linked, Colours: black
1.3 Outer jacket: Flame retardant PE,electron beam cross-linked
resistance against water , UV resistant,Jacket colour: black,red
2
.Temperature range
2.1 Max,temperature at conductor : -40°C up to +120°C
2.2 Temperature range : -40°C up to +90°C
3
.Electrical characteristics
3.1

Nominal AC voltage: 600V
3.2 AC-test-voltage: 3.0KV
3.3 Insulation-Resistance at 15.6°C: 14AWG≥1165 MΩ/km
12AWG≥1000 MΩ/km
10AWG≥843 MΩ/km
4
.
Environmental characteristics
Sunlight-Resistance according clause 30 of UL 854
Vertical flame VW-1 according clause 1100 of UL 1581
5.

Product Description
Product
Code
Number

Size AWG

Conductor dia.
N/mm
Insulation dia.(mm)
Core
colour
Nominal Jacket dia.(mm)
Jacket
colour
Rated current
at
90°C(A)
BY0-A2001
14
43/0.25
4.3
black
/
/
30
BY0-A1001
12
48/0.30
4.8
black
/
/
45
BY0-A0001
10
76/0.30
5.4
black
/
/
55
BY0-A2200
14
43/0.25
4.2
black
5.80
red
30
BY0-A2000
14
43/0.25
4.2
black
5.80
black
30
BY0-A1200
12
48/0.30
4.7
black
6.30
red
45
BY0-A1000
12
48/0.30
4.7
black
6.30
black
45
BY0-A1002
12
65/0.254
4.7
black
6.30
black
45
BY0-A0200
10
76/0.30
5.3
black
6.90
red
55
BY0-A0000
10
76/0.30
5.3
black
6.90
black
55